TECHNICAL DATABASE

Mitsubishi Heavy IndustriesKX/KXR/KXZ – VRF and subcodes

86 search entries, with any different interpretations for the same signal.

Not all subcodes belong to all generations. E30/E64 are specific KXZW; E36-3 KX6; E44 KXZ; E60 KX4/KX6.

Reference models

KX4 · KXR4 · KX6 · KXR6 · KXZ · KXZP · KXZR · KXZX · KXZRX · KXZW

Code / indicatorMeaningDocumented aliases
E1Remote control communication–internal drive—
E10Excessive number of internals on the same command—
E11Master/slave directing of indoor units—
E12Automatic and manual mixing methods—
E16Anomalous indoor fan motor—
E18Address or connection between internal master and slave—
E19Improper operating/condensing pipe control mode—
E2Address duplicated internal drive—
E20Anomalous internal fan speed—
E21Panel switch FDT faulty—
E28Remote control temperature sensor—
E3Outdoor unit signal line—
E30Internal combination – non-compatible source unit (KXZW)—
E31Address duplicated outdoor unit—
E32Step L3 missing or incorrect phase sequence—
E36Temperature sent or liquid return, second subcode—
E36-1Temperature compressor 1, Tho-D1E36 1
E36-2Temperature compressor 2, Tho-D2E36 2
E36-3Liquid return (only KX6)E36 3
E37External heat exchanger/subcooler probes—
E37-1External exchanger probe Tho-R1E37 1
E37-2External exchanger probe Tho-R2E37 2
E37-3External exchanger probe Tho-R3E37 3
E37-4External exchanger probe Tho-R4E37 4
E37-5Probe sottoraffreddatore1 Tho-SCE37 5
E37-6Probe sottoraffreddatore2 Tho-HE37 6
E38External air sensor Tho-A—
E39Temperature probes sent compressors—
E39-1Probe sent compressor 1 Tho-D1E39 1
E39-2Probe sent compressor 2 Tho-D2E39 2
E40High pressure: intervento63H1-1/2—
E41Overheating power transistors—
E41-1Transistor power overheating CM1E41 1
E41-2Transistor power overheating CM2E41 2
E42Current compressor protection—
E42-1Compressor current protection CM1E42 1
E42-2Compressor current protection CM2E42 2
E43Number or capacity of excessive interiors—
E43-1Number of excessively connected indoor unitsE43 1
E43-2Excessive connected total capacityE43 2
E44Liquid return to the compressor (KXZ)—
E44-1Compressor liquid return CM1 (KXZ)E44 1
E44-2Compressor liquid return CM2 (KXZ)E44 2
E45Inverter communication–external control board—
E45-1Communication inverter1–external displayE45 1
E45-2Communication inverter2–external displayE45 2
E46Incompatible address methods in the same network—
E48Outdoor fan motor DC abnormal—
E48-1External fan FMO1E48 1
E48-2External fan FMO2E48 2
E49Too low intake pressure—
E5Communication during operation—
E51High Persistent Transistor Temperature—
E51-1Persistent overheating transistor CM1E51 1
E51-2Persistent overheating transistor CM2E51 2
E53Compressor suction temperature sensor—
E53-1Compressor suction sensor CM1E53 1
E53-2Compressor suction sensor CM2E53 2
E54Low or high pressure measurement, second subcode—
E54-1Low-pressure sensor PSLE54 1
E54-2High-pressure sensor PSHE54 2
E55Temperature sensor under compressor cap—
E55-1Sensor under compressor cap Tho-C1E55 1
E55-2Sensor under compressor cap Tho-C2E55 2
E56Power Transistor Temperature Sensor—
E56-1Tho-P1 Transistor Power SensorE56 1
E56-2Tho-P2 Transistor Power SensorE56 2
E58Compressor outside synchronism—
E58-1Loss synchronism compressor CM1E58 1
E58-2Loss synchronism compressor CM2E58 2
E59Launch of failed compressor—
E59-1Missed compressor starter CM1E59 1
E59-2Missed compressor starter CM2E59 2
E6Internal exchange sensor—
E60Compressor rotor position detection (KX4/KX6)—
E60-1Compressor rotor position CM1 (KX4/KX6)E60 1
E60-2Compressor rotor position CM2 (KX4/KX6)E60 2
E61Communication between external master and slave—
E61-1Communication with external slave1E61 1
E61-2Communication with external slave2E61 2
E63Emergency stop from CnT terminal—
E64Water circulation/antifreeze protection of the source unit (KXZW)—
E64-4Failure to consent water pump/antifreeze shutdown (KXZW)E64 4
E7Internal recovery air sensor—
E75Communication of centralized control—
E9Anomalous condensation discharge—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.