LGMulti V 5 ARUM – full outdoor-unit display code
162 search entries, with any different interpretations for the same signal.
Insert the entire number of the external display. The final digit indicates normalmente1=master,2=slave1,3=slave2. Exceptions documentate511/512: two different capacity errors. A logical code CH242 is distinguished from display242 (CH24 out of slave1).
Reference models
ARUM072BTE5 · ARUM072DTE5 · ARUM096BTE5 · ARUM096DTE5 · ARUM121BTE5 · ARUM121DTE5 · ARUM144BTE5 · ARUM144DTE5 · ARUM168BTE5 · ARUM168DTE5 · ARUM192BTE5 · ARUM192DTE5 · ARUM216BTE5 · ARUM216DTE5 · ARUM241BTE5 · ARUM241DTE5
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| 1041 | Communication between outdoor units master and slave – external master | — |
| 1042 | Communication between outdoor units master and slave – external slave1 | — |
| 1043 | Communication between outdoor units master and slave – external slave2 | — |
| 1051 | Communication board fans–inverter compressor – external master | — |
| 1052 | Communication fan board–inverter compressor – external slave1 | — |
| 1053 | Communication fan board–inverter compressor – external slave2 | — |
| 1061 | IPM outdoor fan protection – external master | — |
| 1062 | Protection IPM outdoor fan – exterior slave1 | — |
| 1063 | Protection IPM outdoor fan – exterior slave2 | — |
| 1071 | Insufficient Voltage DC Fan Inverter – External Master | — |
| 1072 | Voltage DC insufficient fan inverter – external slave1 | — |
| 1073 | Voltage DC insufficient fan inverter – external slave2 | — |
| 1131 | Liquid pipe temperature sensor – external master | — |
| 1132 | Liquid pipe temperature sensor – external slave1 | — |
| 1133 | Liquid pipe temperature sensor – external slave2 | — |
| 1141 | Subcooler input sensor – external master | — |
| 1142 | Subcooler input sensor – external slave1 | — |
| 1143 | Subcooler input sensor – external slave2 | — |
| 1151 | Subcooler output sensor – external master | — |
| 1152 | Subcooler output sensor – external slave1 | — |
| 1153 | Subcooler output sensor – external slave2 | — |
| 1161 | Insufficient oil level or abnormal oil level sensor – external master | — |
| 1162 | Insufficient oil level or abnormal oil level sensor – external slave1 | — |
| 1163 | Insufficient oil level or abnormal oil level sensor – external slave2 | — |
| 1451 | Communication main board–additional external board – external master | — |
| 1452 | Communication main board–additional external board – external slave1 | — |
| 1453 | Communication main board–additional external board – external slave2 | — |
| 1501 | Insufficient delivery superheat and liquid return risk – external master | — |
| 1502 | Insufficient superheat and liquid return risk – external slave1 | — |
| 1503 | Insufficient superheat and liquid return risk – external slave2 | — |
| 1511 | Difference between high and low insufficient pressure – external master | — |
| 1512 | Difference between high and low insufficient pressure – external slave1 | — |
| 1513 | Difference between high and low insufficient pressure – external slave2 | — |
| 1531 | Upper external heat exchanger sensor – external master | — |
| 1532 | External temperature sensor - external slave1 | — |
| 1533 | External temperature sensor - external slave2 | — |
| 1541 | Lower external heat exchanger sensor – external master | — |
| 1542 | External temperature sensor inferior – external slave1 | — |
| 1543 | External temperature sensor inferior – external slave2 | — |
| 1821 | Main/secondary microcontroller communication of the additional board – external master | — |
| 1822 | Main/secondary microcontroller communication of the additional board – external slave1 | — |
| 1823 | Main/secondary microcontroller communication of the additional board – external slave2 | — |
| 1871 | Hydro Kit antifreeze protection – external master | — |
| 1872 | Hydro Kit antifreeze protection – external slave1 | — |
| 1873 | Hydro Kit antifreeze protection – external slave2 | — |
| 1931 | Blower inverter heatsink – external master | — |
| 1932 | Blower inverter heatsink – external slave1 | — |
| 1933 | Blower inverter heatsink – external slave2 | — |
| 1941 | Fan heat dissipator sensor – external master | — |
| 1942 | Fan heat dissipator sensor – external slave1 | — |
| 1943 | Fan heat dissipator sensor – external slave2 | — |
| 2001 | Automatic search for unfinished pipes – display2001 | — |
| 211 | Protection IPM compressor inverter for overcurrent phase – external master | — |
| 212 | Protection IPM compressor inverter for phase overcurrent – external slave1 | — |
| 213 | Protection IPM compressor inverter for phase overcurrent – external slave2 | — |
| 221 | Overcurrent input AC of the inverter board – external master | — |
| 222 | Overcurrent input AC of the inverter board – external slave1 | — |
| 223 | Overcurrent input AC of the inverter board – external slave2 | — |
| 231 | Anomalous voltage on the connection DC of the inverter compressor – external master | — |
| 232 | Anomalous voltage on the connection DC of the inverter compressor – external slave1 | — |
| 233 | Anomalous voltage on the connection DC of the inverter compressor – external slave2 | — |
| 241 | High pressure switch of outdoor unit – external master | — |
| 242 | High pressure switch of the outdoor unit – external slave1 | — |
| 2421 | Centralized control network communication – external master | — |
| 2422 | Centralized control network communication – external slave1 | — |
| 2423 | Centralized control network communication – external slave2 | — |
| 243 | High pressure switch of the outdoor unit – external slave2 | — |
| 251 | External power voltage too high or too low – external master | — |
| 252 | External power voltage too high or too low – external slave1 | — |
| 253 | External power voltage too high or too low – external slave2 | — |
| 261 | Missed start of the inverter compressor – external master | — |
| 262 | Missed start of the inverter compressor – external slave1 | — |
| 263 | Missed start of the inverter compressor – external slave2 | — |
| 291 | Overcurrent inverter compressor – external master | — |
| 292 | Overcurrent inverter compressor – external slave1 | — |
| 293 | Overcurrent inverter compressor – external slave2 | — |
| 321 | Excessive compressor temperature inverter1 – external master | — |
| 322 | Compressor temperature inverter1 excessive – external slave1 | — |
| 323 | Compressor temperature inverter1 excessive – external slave2 | — |
| 331 | Excessive compressor temperature inverter2 – external master | — |
| 332 | Compressor temperature inverter2 excessive – external slave1 | — |
| 333 | Compressor temperature inverter2 excessive – external slave2 | — |
| 341 | High pressure protection detected by control – external master | — |
| 342 | High pressure protection detected by the control – external slave1 | — |
| 343 | High pressure protection detected by the control – external slave2 | — |
| 351 | Intake pressure lower than operating limit – external master | — |
| 352 | Intake pressure lower than operating limit – external slave1 | — |
| 353 | Intake pressure lower than operating limit – external slave2 | — |
| 361 | Insufficient compression ratio – external master | — |
| 362 | Insufficient compression ratio – external slave1 | — |
| 363 | Insufficient compression ratio – external slave2 | — |
| 401 | Inverter compressor current sensor CT – outdoor unit master | — |
| 402 | Inverter compressor current sensor CT – outdoor unit slave1 | — |
| 403 | Inverter compressor current sensor CT – outdoor unit slave2 | — |
| 411 | Temperature sensor sent compressor 1 – external master | — |
| 412 | Temperature sensor sent compressor 1 – external slave1 | — |
| 413 | Temperature sensor sent compressor 1 – external slave2 | — |
| 421 | Low pressure transducer – external master | — |
| 422 | Low pressure transducer – external slave1 | — |
| 423 | Low pressure transducer – external slave2 | — |
| 431 | High pressure transducer – external master | — |
| 432 | High pressure transducer – external slave1 | — |
| 433 | High pressure transducer – external slave2 | — |
| 441 | External air temperature sensor – external master | — |
| 442 | External air temperature sensor – external slave1 | — |
| 443 | External air temperature sensor – external slave2 | — |
| 451 | External temperature sensor – external master | — |
| 452 | External temperature sensor – external slave1 | — |
| 453 | External temperature sensor – external slave2 | — |
| 461 | Intake temperature sensor – external master | — |
| 462 | Suction temperature sensor – external slave1 | — |
| 463 | Suction temperature sensor – external slave2 | — |
| 471 | Temperature sensor sent compressor 2 – external master | — |
| 472 | Temperature sensor sent compressor 2 – external slave1 | — |
| 473 | Temperature sensor sent compressor 2 – external slave2 | — |
| 491 | Temperature sensor IPM – external master | — |
| 492 | Temperature sensor IPM – external slave1 | — |
| 493 | Temperature sensor IPM – external slave2 | — |
| 501 | Power phase of the missing outdoor unit – external master | — |
| 502 | Power phase of the missing outdoor unit – external slave1 | — |
| 503 | Power phase of the missing outdoor unit – external slave2 | — |
| 511 | Internal/external capacity ratio | — |
| 512 | Excessive capacity on recuperator/retrieval time | — |
| 521 | Communication main board–inverter of outdoor unit – external master | — |
| 522 | Communication main board–inverter of outdoor unit – external slave1 | — |
| 523 | Communication main board–inverter of outdoor unit – external slave2 | — |
| 531 | Outdoor unit communication – indoor unit – external master | — |
| 532 | Outdoor unit communication – indoor unit – external slave1 | — |
| 533 | Outdoor unit communication – indoor unit – external slave2 | — |
| 571 | Inverter does not receive data from the main board – external master | — |
| 572 | Inverter does not receive data from the main board – external slave1 | — |
| 573 | Inverter does not receive data from the main board – external slave2 | — |
| 601 | EEPROM outdoor inverter board – external master | — |
| 602 | EEPROM outdoor inverter board – external slave1 | — |
| 603 | EEPROM of external inverter board – external slave2 | — |
| 621 | High temperature of the compressor inverter heatsink – external master | — |
| 622 | High temperature of the compressor inverter heatsink – external slave1 | — |
| 623 | High temperature of the compressor inverter heatsink – external slave2 | — |
| 651 | Sensor temperature heatsink inverter – external master | — |
| 652 | Sensor temperature heatsink inverter – external slave1 | — |
| 653 | Sensor temperature heatsink inverter – external slave2 | — |
| 671 | External fan blocked – external master | — |
| 672 | External fan blocked – external slave1 | — |
| 673 | External fan blocked – external slave2 | — |
| 711 | Outdoor inverter current sensor CT – outdoor unit master | — |
| 712 | Outdoor inverter current sensor CT – outdoor unit slave1 | — |
| 713 | Outdoor inverter current sensor CT – outdoor unit slave2 | — |
| 751 | Outdoor fan current sensor CT – outdoor unit master | — |
| 752 | Outdoor fan current sensor CT – outdoor unit slave1 | — |
| 753 | Outdoor fan current sensor CT – outdoor unit slave2 | — |
| 771 | External fan overcurrent – external master | — |
| 772 | External fan overcurrent – external slave1 | — |
| 773 | External fan overcurrent – external slave2 | — |
| 791 | Lack initial determination of fan position – external master | — |
| 792 | Lack initial determination of fan position – external slave1 | — |
| 793 | Lack initial determination of fan position – external slave2 | — |
| 861 | EEPROM of external main board – external master | — |
| 862 | EEPROM external main board – external slave1 | — |
| 863 | EEPROM external main board – external slave2 | — |
| 871 | EEPROM outdoor fan board – external master | — |
| 872 | EEPROM outdoor fan board – external slave1 | — |
| 873 | EEPROM outdoor fan board – external slave2 | — |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.