343High pressure protection detected by the control – external slave2
Multi V 5 ARUM – full outdoor-unit display code
Insert the entire number of the external display. The final digit indicates normalmente1=master,2=slave1,3=slave2. Exceptions documentate511/512: two different capacity errors. A logical code CH242 is distinguished from display242 (CH24 out of slave1).
Documented models
ARUM072BTE5 · ARUM072DTE5 · ARUM096BTE5 · ARUM096DTE5 · ARUM121BTE5 · ARUM121DTE5 · ARUM144BTE5 · ARUM144DTE5 · ARUM168BTE5 · ARUM168DTE5 · ARUM192BTE5 · ARUM192DTE5 · ARUM216BTE5 · ARUM216DTE5 · ARUM241BTE5 · ARUM241DTE5
What it means
The complete display 343 identifies the main code CH34 on the outdoor unit slave2. High pressure protection detected by the control. The pressure detected does not fall within the permitted conditions. The cause may be in the refrigerant circuit or in its measure.
Possible causes to distinguish
- Non-regular refrigerant circuit conditions, valve or air flow to check.
- Sensor/pressostat, connections and reading circuit to be checked.
What to tell the repair lab
Record the full code and photograph the display and the nameplates of the indoor and outdoor units. Tell the laboratory when the shutdown occurs and whether it affects one or more units; avoid repeated restarts.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- The technician compares actual pressure and value acquired by the control unit.
- Check thermal exchange and refrigerant circuit before concluding that the defect is electronic.
Record the full code and identify the affected outdoor unit; do not omit the address digit.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: LG Multi V 5 Outdoor Unit Service Manual · page 129.