E37External exchange probe
FDTC/FDT/FDU/FDUM/FDEN – PAC-T-118
The headings specify the restrictions for outdoor units SRC40–60 and FDC71–250.
Documented models
FDTC40ZHXV · FDTC50ZHXV · FDT40ZHXV · FDEN40ZHXV · FDUM50ZHXV · SRC40–60 · FDC71–250
What it means
External exchanger probe. The controller is receiving an unreliable measurement; the code alone does not prove that the electronic board is faulty.
Possible causes to distinguish
- Open-circuit sensor or wiring, an intermittent connector, or a short-circuited component.
- Check the board’s sensor input circuit if the sensor and wiring meet specifications.
What to tell the repair lab
Record the full code and photograph the display and the nameplates of the indoor and outdoor units. Tell the laboratory when the shutdown occurs and whether it affects one or more units; avoid repeated restarts.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- Identify the exact sensor and compare its measured value with the characteristic curve in the manual.
- Check the connectors, continuity and input circuit before attributing the fault to the PCB.
Applicability shown in the table: All combinations of the table.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: MHI Packaged Air Conditioner – Manuale 08 PAC-T-118, aggiornato luglio 2011 · page 266 (PDF287); diagnostic pp285–322.