TECHNICAL DATABASE

Mitsubishi Heavy IndustriesFDTC/FDT/FDU/FDUM/FDEN – PAC-T-118

31 search entries, with any different interpretations for the same signal.

The headings specify the restrictions for outdoor units SRC40–60 and FDC71–250.

Reference models

FDTC40ZHXV · FDTC50ZHXV · FDT40ZHXV · FDEN40ZHXV · FDUM50ZHXV · SRC40–60 · FDC71–250

Code / indicatorMeaningDocumented aliases
E1Wired command communication – indoor unit—
E10Too many indoor units on the same command—
E14Communication between internal master and slave—
E16Anomalous indoor fan—
E19Set operation control / pipe incorrect condensation—
E28Remote control temperature sensor—
E33Primary current of anomaly inverter—
E35Cooling overload—
E36Excessed temperature—
E37External exchange probe—
E38External air supply—
E39Probe of compressor—
E40High pressione63H1 high pressure switch—
E41Overheating power transistors—
E42Stop for overcurrent compressor—
E45Communication between external control and inverter—
E47Overcurrent inverter protection—
E48Outdoor fan DC anomaly—
E49Low pressure or low abnormal pressure sensor—
E5Indoor/outdoor communication during operation—
E51Anomalous inverter—
E53Suction temperature sensor—
E54Anomalous Low Pressure Sensor—
E55Temperature sensor under the compressor cap—
E57Insufficient cooling or closed service valve—
E59Unsuccessful compressor start—
E6Internal temperature sensor—
E60Locked compressor roll—
E7Resumption air temperature sensor—
E8Overload in heating—
E9Anomalous condensation discharge—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.