SanyoMini ECO-i SPW-CR365/605 GXH
48 search entries, with any different interpretations for the same signal.
Applicability to be confirmed on models SPW-DXHN8 and other platforms. A similarity of the board does not show diagnostic equivalence.
Reference models
SPW-CR365GXH56 · SPW-CR605GXH56 · SPW-CR365GXH8 · SPW-CR605GXH8
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| E01 | Remote control data reception | — |
| E02 | Anomalous data transmission from remote control | — |
| E03 | Communication between internal drive and remote control | — |
| E04 | Indoor unit does not receive data from the outside | — |
| E06 | Outdoor unit does not receive data from the inside | — |
| E08 | Address duplicated internal drive | — |
| E09 | Two main remote controls | — |
| E12 | Prevented automatic addressing | — |
| E15 | Insufficient number of indoor units | — |
| E16 | Excessive indoor unit number | — |
| E18 | Internal communication in the anomaly group | — |
| E20 | No indoor units detected during addressing | — |
| E24 | Relay module does not receive data from the outside | — |
| E25 | Address uncorrected outdoor unit | — |
| E29 | Outdoor unit does not receive data from the relay module | — |
| E30 | Anomalous external serial transmission | — |
| F01 | Internal exchange probe E1 | — |
| F02 | Internal exchange probe E2 | — |
| F03 | Internal exchange probe E3 | — |
| F04 | Compressor temperature sensor | — |
| F07 | Outdoor heat exchanger liquid probe C1 | — |
| F08 | External air temperature sensor | — |
| F10 | Indoor return air sensor TA | — |
| F11 | Indoor supply air sensor BL | — |
| F12 | Compressor suction sensor TS | — |
| F16 | High pressure transducer | — |
| F29 | Memory EEPROM indoor unit | — |
| F31 | Memory EEPROM outdoor unit | — |
| H03 | Compressor current sensor CT: open or short circuit | — |
| H31 | Module protection HIC/IPM compressor | — |
| L02 | Non-correct internal and outdoor unit matching | — |
| L03 | Main address duplicated in the group | — |
| L04 | Address circuit refrigerator duplicated | — |
| L05 | Priority duplicate mode on priority command | — |
| L06 | Priority duplicate mode on the non-priority command | — |
| L07 | Group cabling on individually configured units | — |
| L08 | Address indoor unit absent | — |
| L09 | Unset internal drive capacity | — |
| L10 | Unset outdoor unit capacity | — |
| L17 | Type of outdoor unit incompatible | — |
| P03 | Anomalous compressor temperature | — |
| P05 | Sequence or presence of abnormal phases | — |
| P13 | Loss detected synchronism | — |
| P14 | Oxygen sensor switch if present | — |
| P16 | Low frequency compressor overcurrent | — |
| P22 | Anomaly external fan | — |
| P26 | High frequency compressor overcurrent | — |
| P29 | Non-start inverter compressor | — |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.