What it means
One of the TH3, TH6, TH7 or TH8 is open or short. The numerical detail identifies the probe.
Possible causes to distinguish
- fault sensor
- Wiring or faulty connector
- Reading circuit
What to tell the repair lab
Photograph the fault indication and the nameplate. Tell the laboratory when the shutdown occurs and whether it recurs. Checks on circuit boards, wiring and the refrigerant circuit require a qualified technician.
Technical guidance
Guidance for qualified personnel, to be checked against the unit’s service manual.
- Check the detail:5105 TH3,5107 TH6,5106 TH7,5110 TH8; use the correct sensor curve.
Does this necessarily mean the board is faulty?
The code indicates a condition detected by the control. Before evaluating the electronic repair, it is necessary to distinguish the circuit concerned, the connections and operating conditions. Model and description of the defect allow the repair lab to evaluate the case.
Source for this interpretation: Mitsubishi Electric OCH415F – Mr Slim PUHZ-P100/125/140 · page 52.