LGMulti V 5 ARUM – main CH codes
82 search entries, with any different interpretations for the same signal.
The main codes are separate from the final outdoor-unit address digit: 211 = error 21 on the master unit; 212 = error 21 on slave 1. Enter CH21 for the main code. CH242 (central network) is different from display code 242 (24 on slave 1).
Reference models
ARUM072BTE5 · ARUM072DTE5 · ARUM096BTE5 · ARUM096DTE5 · ARUM121BTE5 · ARUM121DTE5 · ARUM144BTE5 · ARUM144DTE5 · ARUM168BTE5 · ARUM168DTE5 · ARUM192BTE5 · ARUM192DTE5 · ARUM216BTE5 · ARUM216DTE5 · ARUM241BTE5 · ARUM241DTE5
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| CH01 | Ambient air sensor or remote indoor unit probe | 01, 1, CH1 |
| CH02 | Indoor unit pipe input sensor | 02, 2, CH2 |
| CH03 | Communication between zone command and indoor unit | 03, 3, CH3 |
| CH04 | Excessive level of condensation in the indoor unit | 04, 4, CH4 |
| CH05 | Indoor/outdoor communication failure detected by the indoor unit | 05, 5, CH5 |
| CH06 | Hydro Kit internal pipe or liquid side output sensor | 06, 6, CH6 |
| CH07 | Incompatible operating modes between indoor units (heat pump systems) | 07, 7, CH7 |
| CH08 | Hydro Kit hot water storage temperature sensor | 08, 8, CH8 |
| CH09 | EEPROM or internal drive options board | 09, 9, CH9 |
| CH10 | Internal fan motor BLDC: rotation or absent feedback | 10, CH10 |
| CH104 | Communication between master and slave outdoor units | 104, CH104 |
| CH105 | Communication fan board–inverter compressor | 105, CH105 |
| CH106 | Outdoor Fan Protection IPM | 106, CH106 |
| CH107 | Insufficient Voltage DC Fan Inverter | 107, CH107 |
| CH11 | Communication Hydro Kit–Inverter compressor box | 11, CH11 |
| CH113 | Liquid pipe temperature sensor | 113, CH113 |
| CH114 | Subcooler input sensor | 114, CH114 |
| CH115 | Subcooler output sensor | 115, CH115 |
| CH116 | Insufficient oil level or abnormal oil level sensor | 116, CH116 |
| CH12 | Hydro Kit inverter adapter | 12, CH12 |
| CH13 | Hydro Kit Solar Tubing Sensor | 13, CH13 |
| CH14 | Hydro flow system | 14, CH14 |
| CH145 | Communication main board–additional external board | 145, CH145 |
| CH15 | Water temperature output Hydro Kit over limit | 15, CH15 |
| CH150 | Insufficient superheat and liquid return risk | 150, CH150 |
| CH151 | Difference between high and low insufficient pressure | 151, CH151 |
| CH153 | Upper external temperature sensor | 153, CH153 |
| CH154 | Lower external temperature sensor | 154, CH154 |
| CH16 | Hydro Kit water and environment piping sensors | 16, CH16 |
| CH17 | Hydro Kit water input sensor or external air channeled | 17, CH17 |
| CH18 | Hydro Kit water output sensor | 18, CH18 |
| CH182 | Main/secondary microcontroller communication of the additional board | 182, CH182 |
| CH187 | Hydro Kit antifreeze protection | 187, CH187 |
| CH193 | Fan inverter heat sink overheating | 193, CH193 |
| CH194 | Fan heat dissipator sensor | 194, CH194 |
| CH200 | Automatic search for unfinished pipes | 200, CH200 |
| CH201 | Liquid sensor of heat recovery unit | 201, CH201 |
| CH202 | Heat recovery unit subcooler input sensor | 202, CH202 |
| CH203 | Heat recovery unit subcooler outlet sensor | 203, CH203 |
| CH204 | Outdoor unit communication–heat recuperator | 204, CH204 |
| CH205 | Communication heat recovery unit 2A–modem485 | 205, CH205 |
| CH206 | Duplicate address of the recoverer of calore2A | 206, CH206 |
| CH21 | Protection IPM compressor inverter for overcurrent phase | 21, CH21 |
| CH22 | Overcurrent input AC of the inverter board | 22, CH22 |
| CH23 | Anomalous voltage on the DC connection of the compressor inverter | 23, CH23 |
| CH230 | Refrigerant leak detection sensor | 230, CH230 |
| CH237 | Indoor/outdoor communication: network verification RS-485 | 237, CH237 |
| CH238 | Indoor/outdoor communication: external board verification | 238, CH238 |
| CH24 | Outdoor unit high pressure switch | 24, CH24 |
| CH242 | Centralized Control Network Communication | 242, CH242 |
| CH25 | External power voltage too high or too low | 25, CH25 |
| CH26 | Missed start of the inverter compressor | 26, CH26 |
| CH29 | Overcurrent of inverter compressor | 29, CH29 |
| CH32 | Compressor temperature inverter1 excessive | 32, CH32 |
| CH33 | Compressor temperature inverter2 excessive | 33, CH33 |
| CH34 | High pressure protection detected by the control | 34, CH34 |
| CH35 | Intake pressure lower than operating limit | 35, CH35 |
| CH36 | Insufficient compression ratio | 36, CH36 |
| CH40 | Inverter compressor current sensor CT | 40, CH40 |
| CH41 | Temperature sensor sent compressor 1 | 41, CH41 |
| CH42 | Low pressure transducer | 42, CH42 |
| CH43 | High pressure transducer | 43, CH43 |
| CH44 | External air temperature sensor | 44, CH44 |
| CH45 | External temperature sensor | 45, CH45 |
| CH46 | Suction temperature sensor | 46, CH46 |
| CH47 | Temperature sensor sent compressor 2 | 47, CH47 |
| CH49 | Temperature sensor IPM | 49, CH49 |
| CH50 | Power phase of the missing outdoor unit | 50, CH50 |
| CH51 | Connected capacity outside system or recuperator limits | 51, CH51 |
| CH52 | Communication main board–inverter of outdoor unit | 52, CH52 |
| CH53 | Outdoor unit communication–indoor unit | 53, CH53 |
| CH57 | Inverter does not receive data from the main board | 57, CH57 |
| CH60 | EEPROM outdoor inverter board | 60, CH60 |
| CH62 | High temperature of the compressor inverter heatsink | 62, CH62 |
| CH65 | Sensor temperature dissipator inverter | 65, CH65 |
| CH67 | External fan locked | 67, CH67 |
| CH71 | Outdoor inverter current sensor CT | 71, CH71 |
| CH75 | Outdoor fan current sensor CT | 75, CH75 |
| CH77 | External fan overcurrent | 77, CH77 |
| CH79 | Lack initial determination of fan position | 79, CH79 |
| CH86 | EEPROM of external main board | 86, CH86 |
| CH87 | EEPROM outdoor fan board | 87, CH87 |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.