TECHNICAL DATABASE

CarrierAquaSnap 30AWH015 – LEDs Display 1/Display 2

24 search entries, with any different interpretations for the same signal.

Each group describes D800,D801,D802,D803,D804; D805 green is excluded.1=light,0=spento,F=flaking. LED-11001-00F00 indicates Display 1 followed by Display 2. With both gruppi00000 the document indicates normal status. Technical reading.

Reference models

30AWH015HB · 30AWH015XB · 30AWH015NX

Code / indicatorMeaningDocumented aliases
LED-00101-00F00Intervention compressor body thermostat—
LED-00101-0F000Locked compressor—
LED-00101-F0000Anomaly of the compressor—
LED-00101-FF000Anomalous current detection circuit—
LED-01101-0F000Unconfigured model—
LED-01101-F0FFFCommunication between microcontrollers—
LED-01101-FFFFFOther anomaly, including compressor disorder—
LED-11001-000F0Outdoor air sensor TO—
LED-11001-00F00Discharge sensor TD—
LED-11001-00FF0Suction sensor TS—
LED-11001-0FF00Heat exchanger sensor TE—
LED-11001-F0FF0Heat sink sensor TH—
LED-11001-FFF00Heat exchanger sensor TL—
LED-11001-FFFF0Incorrect wiring of sensors TE/TS—
LED-11001-FFFFFEEPROM anomaly—
LED-11101-00F0FHigh pressure protection—
LED-11101-0F0FFCortocircuit power element—
LED-11101-0FF0FAnomalous fan system—
LED-11101-F0F00Anomalous power supply—
LED-11101-F0FFFAnomalous Position Detection Circuit—
LED-11101-FF000Anomalous discharge temperature—
LED-11101-FF00FFour-way valve changeover not confirmed—
LED-11101-FFF00Overheated divider—
LED-11101-FFFF0Detection prediction/loss refrigerant—

Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.