TECHNICAL DATABASE
CarrierAquaSnap 30AWH – GMC codes
23 search entries, with any different interpretations for the same signal.
Numerical code issued by the LED of the GMC board; it is not the simultaneous pattern of the LED inverter.
Reference models
30AWH004HB · 30AWH006HB · 30AWH008HB · 30AWH012HB · 30AWH015HB · 30AWH004XB · 30AWH006XB · 30AWH008XB · 30AWH012XB · 30AWH015XB · 30AWH004NX · 30AWH006NX · 30AWH008NX · 30AWH012NX · 30AWH015NX
| Code / indicator | Meaning | Documented aliases |
|---|---|---|
| 10 | EEPROM corrupt GMC board | GMC10, GMC-10 |
| 13 | Communication RS485 absent | GMC13, GMC-13 |
| 14 | Inverter signal absent or thermal protection | GMC14, GMC-14 |
| 15 | Water outlet sensor LWT | GMC15, GMC-15 |
| 16 | Alarm output test | GMC16, GMC-16 |
| 17 | Inverter outdoor air sensor TO | GMC17, GMC-17 |
| 18 | Short power stage protectionG-Tr | GMC18, GMC-18 |
| 2 | Active safety input | GMC2, GMC-2 |
| 20 | Compressor position detection circuit | GMC20, GMC-20 |
| 21 | Current inverter sensor | GMC21, GMC-21 |
| 22 | Heat exchanger sensors TE/TS | GMC22, GMC-22 |
| 23 | Discharge sensor TD | GMC23, GMC-23 |
| 24 | Anomaly external fan | GMC24, GMC-24 |
| 26 | Other unit fault | GMC26, GMC-26 |
| 27 | Locked compressor | GMC27, GMC-27 |
| 28 | Anomalous discharge temperature | GMC28, GMC-28 |
| 29 | Anomalous operation of the compressor | GMC29, GMC-29 |
| 3 | Water inlet sensor EWT | GMC3, GMC-3 |
| 4 | Refrigerant temperature sensor TR | GMC4, GMC-4 |
| 5 | Outdoor air sensor connected to the GMC board | GMC5, GMC-5 |
| 6 | Communication GMC–command NUI | GMC6, GMC-6 |
| 7 | NUI controller room sensor | GMC7, GMC-7 |
| 9 | Flow or water pump | GMC9, GMC-9 |
No entries match the filter.
Items LED and MEM describe faulty indicator lights and memory; they are not display codes. The operating conditions in the manual remain decisive.